1/2 EMT take-up: how to bend a 90 in 1/2 EMT

Bender charts · Published November 8, 2026

Take-up, 1/2″ EMT

5″

Subtract it from the stub height you want. The result is your mark, measured from the end of the stick.

Bender values: Klein Tools Conduit Bender Guide (56203–56207, 56211), page 2.

90° stub-up on a Klein 56203, 1/2″ EMT: mark 1 at 7″7″END1END1
90° stub-up on a Klein 56203, 1/2″ EMT: mark 1 at 7″. Numbered in bending order.
Bendbook’s bender list, with a Klein 3/4″ EMT bender picked

Your own marks

Bendbook draws every mark for the bender in your hand, numbered in bending order. Offline.

The take-up for a 1/2 inch EMT hand bender is 5″. Take-up, also called the deduct, is the length the bender uses up in a 90°. To bend a stub, subtract the take-up from the stub height you want, mark the stick that far from the end, line the mark up with the arrow and pull to 90°.

Take-up of 1/2 inch EMT benders

BenderTake-upRadiusSource
Gardner Bender 9605″3-11/16″Gardner Bender Hand Bender How To Guide (960/961/962), page 1
Greenlee 840A5″4-3/16″Greenlee Use Guide, Site-Rite 840–844 hand benders, page 4
Greenlee 840F5″4-3/16″Greenlee Use Guide, Site-Rite 840–844 hand benders, page 4
Greenlee 844A5″4-3/16″Greenlee Use Guide, Site-Rite 840–844 hand benders, page 4
Ideal 74-001not published——
Ideal 74-031not published——
Klein 562035″—Klein Tools Conduit Bender Guide (56203–56207, 56211), page 2
Klein 562065″—Klein Tools Conduit Bender Guide (56203–56207, 56211), page 2

Every 1/2 inch EMT bender in this table that publishes a take-up prints the same one, so the mark for a given stub is the same on any of them. The maker publishes no take-up for the Ideal 74-001 and 74-031. If you bend with one of those, measure your own take-up from a test stub, as described under Questions below.

A bender for another size or for rigid has its own take-up. Check the model number on the head before you trust the number. For other sizes, see the hand bender take-up chart.

Where to mark common stubs

The mark is the stub height less the take-up, measured from the end of the stick that will rise.

Stub heightMark from the endLine up with
8″3″Arrow
10″5″Arrow
12″7″Arrow
14″9″Arrow
16″11″Arrow
18″13″Arrow
20″15″Arrow
24″19″Arrow
30″25″Arrow

Take-up 5″: Klein Tools Conduit Bender Guide (56203–56207, 56211), page 2.

Worked example: a 12 inch stub

Worked example90° stub-up on a Klein 56203, 1/2″ EMT, numbers as printed in the maker’s guide
Stub height
12″
MarkFrom the endLine up withBendDirection
17″Arrow90°First bend
Take-up
5″

Bender values: Klein Tools Conduit Bender Guide (56203–56207, 56211), page 2.

Calculate this bend in Bendbook. Pick your bender, type your measurements, and every mark is drawn on the stick for you.

The stub height runs from the end of the stick to the back of the bend, the outside of the 90. That is what the take-up assumes, so measure the finished stub the same way when you check it.

Steps

  1. Measure the stub height you need. Decide which end of the stick will rise.
  2. Subtract the take-up, 5″, from the stub height. Mark the stick that far from the end that will rise.
  3. Draw the mark all the way around the stick, so you can see it from the side.
  4. Seat the stick in the bender and line the mark up with the arrow.
  5. Before you pull, check that the stub will come up from the end you measured from. If it would come up from the other end, take the stick out and turn it around.
  6. Keep your foot heavy on the heel and pull the handle in one steady motion until the stub reaches 90°.
  7. Check the stub with a level, then measure from the end of the stick to the back of the bend.

Mistakes that cost a stick

  • Forgetting the take-up. Mark at the full stub height and the stub comes out too tall by the take-up.
  • Measuring from the wrong end. The mark is measured from the end that will rise. Check it before you pull.
  • Lining the mark up with the wrong head mark. For a stub, the mark goes on the arrow. The degree lines show how far the bend has gone; do not line the mark up with them.
  • Using the wrong size's take-up. Take-up changes with conduit type and size. Use the 1/2 inch EMT value, not the value for 3/4 inch EMT or rigid.
  • Over-bending. A stub pulled past 90° has to be eased back, which is hard to do cleanly. Stop at 90° and check.
  • Forgetting the bend count. Between pull points, EMT is covered by NEC 358.24. Count your bends before you commit.

Questions

What is take-up on 1/2 inch EMT?

It is the length the bender uses up to form a 90°. You subtract it from the stub height you want to find where the mark goes on the stick.

Is the take-up the same on every 1/2 inch EMT bender?

For every bender in the table that publishes one, yes. Find your model in the table and make sure you are reading the 1/2 inch EMT line.

My bender has no published take-up. How do I find it?

Bend one test stub. Put a mark a known distance from the end, line it up with the arrow and bend a 90. Measure the stub from the end to the back of the bend. The stub height less the distance to your mark is your take-up. Write it on the bender.

Do I need take-up for an offset?

No. Offsets use a multiplier and shrink instead. See conduit shrink per inch of offset and the multiplier guides for 22-1/2 degrees and 30 degrees. For more on stubs, see how to bend a 90 degree stub-up.

Check against your own bender. The numbers on this page use the values the maker publishes for the bender named; where the maker prints none, they are worked out from the geometry of the bend. Shoes wear, conduit varies and springback differs, so make one test bend and adjust before you bend the run.